HVM (High Voltage Motors)


E-Series Specification

 

  Standard Option
Type Cage Induction -
Frame Sizes 315 to 630 -
Output 75 - 2500kW @ 4-pole speed  
Voltage 3300, 4160, 6600 Other voltages to 11kV
Mounting Horizontal or Vertical -
Frequency 50Hz or 60Hz Variable Frequency Supply
Poles 2 to 8 Others, Multiple-pole
Cooling Air Cooled -
Ingress Protection IP44 IP56
Mounting (EN 60034-7) IM2001 - Horizontal Foot, IM3011 - Vertical Flange IM2001 - Horz. Foot and Flange, IM3811 - Vertical Skirt
Temperature Rise Class B Class F
Duty S1 Others
Insulation Class F, VPI Class H, VPI
Bearings Grease Lubricated, Rolling Element Bearings Oil - Lubricated, Rolling Element Bearings
Main Terminal Box Phase Insulated (EEx e) Phase Segregated (EEx d), Elastomeric termination (EEx e)
Ambient Temperature -30OC to +55OC Please refer to manufacturer.
Starting Design N Design D, Low Starting Current, High Starting Torque
Starting Method DOL Others
Noise Level, Mean Sound Pressure Level, @ 1m, No Load 85 dB(A) Refer to manufacturer for lower noise level.
Vibrations Grade R to EN60034.14 API 541 Ed 3
Standards EN60034-1, IEC 72: Pt 2 NEMA MG1, Customer Specific
Area Classification EEx d to EN50.018, for group IIA & IIB. Group IIC Gases, Australian standards, AS2380: Pt 1: 1989, AS2380: Pt 2: 1991


Back